Signal Name Description Condition Impact
Wall connector relay coils are at an unexpected voltage, usually due to overheating or other damage
Relay coil voltage is out of the expected range for the current state of the relays
Charging is interrupted
Wall connector requires configuration via the web UI before it can operate
Wall connector does not have necessary parameters configured
The Wall connector will not charge vehicles
Contactors opened due to measured current exceeding configured unit current limit or sharing network allocated current.
Measured current exceeds configured limit or sharing network allocation by 10 percent + 1 A root mean square (RMS).
Wall connector will stop charging and retry at most 3 times before waiting for the cable to be cycled.
Neutral conductor is grounded on vehicle side.
Neutral conductor impedance to ground on vehicle side is less than 2 Ohms with contactors open.
Wall connector will not allow charging if there is a short between neutral and protective earth when a vehicle is connected before closing contactors.
Ground fault detection circuit self-test failed.
Ground fault detection circuit self-test failed.
Wall connector will not allow charging until the ground fault circuit self-test passes.
Ground fault current exceeded threshold.
Ground fault current exceeded threshold.
Wall connector will not allow charging until ground fault current path is corrected and the test rerun.
Vehicle-side protective earth is disconnected from wall connector.
Vehicle-side protective earth is disconnected or high impedance.
Wall connector will not allow charging until vehicle-side protective earth is connected.
Wall connector protective earth is disconnected or grounding scheme dual in-line package (DIP) switch is set incorrectly.
Wall connector alternating current (AC) input side ground impedance is above threshold.
Wall connector will not allow charging until the protective earth connection is corrected.
Center Console Control Module (CCCM) CPU critical register integrity check.
CCCM detects CPU critical register integrity check.
No vehicle impact. This alert is intended for logging purposes.
Center Console Control Module (CCCM) Read Only Memory (ROM) data read/write integrity failure.
CCCM detects ROM data read/write integrity failure.
No vehicle impact. This alert is intended for logging purposes.
Center Console Control Module (CCCM) Random Access Memory (RAM) data read/write integrity failure.
CCCM detects RAM data read/write integrity failure.
No vehicle impact. This alert is intended for logging purposes.
Wall connector internal voltage reference is out of acceptable range.
Internal voltage reference leaves acceptable range.
Wall connector will not operate.
Output voltage, current, and energy monitoring failure.
Metering hardware fails to initialize.
Wall connector cannot detect welds, over-current, or meter energy. Wall connector will not operate.
Alternating current (AC) line phase-locked loop (PLL) failed to lock. Check grid frequency and quality.
PLL was unable to identify valid grid frequency and phase.
Ground fault circuit interrupter (GFCI) cannot function without locked PLL, wall connector will not operate.
Master and slave units in the sharing network have different nameplate current ratings.
Wall connector nameplate current rating differs from the other wall connector in the sharing network.
Wall connector will not operate.
Pilot level invalid.
Pilot level transitions to invalid voltage level.
Wall connector will not operate while pilot level is invalid.
Invalid rotary dial selection.
Wall connector current limit selection dial is set to an invalid position.
Wall connector will not operate.
Wall connector charge handle temperature sensor shorted, open, or too cold.
Charge handle temperature sensor measured as open or short circuit.
Wall connector will not operate.
Wall connector input terminal temperature sensor shorted, open, or too cold.
Input terminal temperature sensor measured as open or short circuit.
Wall connector will not operate.
Wall connector printed circuit board assembly (PCBA) temperature sensor shorted, open, or too cold.
PCBA temperature sensor measured as open or short circuit.
Wall connector will not operate.